Modbus
Some devices, such as meters (meters
) or chargers (chargers
), are connected and addressed using the Modbus protocol.
The meter
configuration includes the type of physical connection (interface), optional technical interface parameters, the Modbus protocol used, the unique Modbus ID of the device on the bus, and the number and type of the register to be read or written.
It is important to note that there are three different Modbus protocols: Modbus RTU, Modbus ASCII, and Modbus TCP. These can technically be transmitted over different types of interfaces. The classic version is Modbus RTU over a serial RS485 bus interface, commonly used with most meters or some chargers. Devices with a native network interface (Ethernet/WiFi), on the other hand, are typically addressed using the Modbus TCP protocol.
If a serial Modbus device needs to be connected through an interface converter via a network (Ethernet/WiFi/PowerLAN), Modbus RTU protocol over a TCP/IP connection is established. The Modbus RTU protocol is directly transmitted over the network (i.e., "tunnelled"). Even though the transport method (TCP/IP) is the same, the protocol is NOT the same as Modbus TCP. It's essential to distinguish between the protocol and the transport method. "Modbus (RTU) over TCP" is different from Modbus TCP!
Caution: There are more complex interface converters that can optionally translate the Modbus protocol itself between Modbus RTU and Modbus TCP! If this feature is active, evcc must communicate with the converter using Modbus TCP, while the converter communicates with the serial device via Modbus RTU and bidirectionally translates the two protocols. In this case, careful attention must be paid to the device specification and configuration; otherwise, communication might not work!
In the case of a configuration with an interface converter, the serial bus configuration is determined only on the converter. The evcc configuration then concerns only the section up to the converter.
Physical Connection
Serial Connection (RS485)
If the device is directly connected via an RS485 adapter (Modbus RTU), device
and the serial communication parameters baudrate
and comset
must be specified according to the device configuration. Please refer to the respective user manual, data sheets, or system settings.
Multiple devices with identical communication parameters can be operated on a serial RS485 bus if each device is assigned a unique Modbus ID. If not all devices on a bus can be configured with uniform communication settings (but with different IDs), splitting into multiple independent bus systems is necessary.
Mixing devices with different serial communication parameters on a bus is not possible and leads to unpredictable communication errors.
For example:
source: modbus
id: 1
device: /dev/ttyUSB0
baudrate: 38400
comset: "8E1"
Direct Network Connection
If the device is directly connected via a native network connection (Modbus TCP), a uri
consisting of HOSTNAME:PORT or IP:PORT must be provided:
For example:
source: modbus
id: 1
uri: 192.168.0.11:502
Serial Device via Network Connection (with Interface Converter)
If a serial device is connected via an intermediate transparent RS485-IP interface converter (without protocol translation), the protocol must also be switched to Modbus RTU over the TCP/IP connection using rtu: true
.
For example:
source: modbus
id: 1
uri: 192.168.0.10:502
rtu: true # Modbus RTU over TCP
Predefined Devices
The integrated predefined device models model
are identical to MBMD:
ABB ABB A/B-Series meters DDM DDM18SD DZG DZG Metering GmbH DVH4013 meters IEM3000 Schneider Electric iEM3000 series INEPRO Inepro Metering Pro 380 JANITZA Janitza meters MPM Bernecker Engineering MPM3PM meters ORNO1P ORNO WE-514 & WE-515 ORNO1P504 ORNO WE-504 ORNO3P ORNO WE-516 & WE-517 SBC Saia Burgess Controls ALE3 meters SDM Eastron SDM630/120/72DMv2 SDM220 Eastron SDM220 SDM230 Eastron SDM230 SDM72 Eastron SDM72 SEMTR SolarEdge SE-MTR-3Y
Any model
that deviates from these is
treated as a SunSpec device type.
Use value
to define the value to be read from the device. All supported values are predefined in MBMD.
In the case of a SunSpec-compatible inverter or meter, the values to be read are specified in the format model:[block:]point
according to the SunSpec definition. For example, querying the DC power on the second string of a three-phase PV inverter (corresponding to SunSpec Model 103) is done as follows: value: 103:2:W
.
The device model
and the slave ID id
are always required:
For example:
source: modbus
---
model: sdm
value: Power
scale: -1 # floating point factor applied to result, e.g. for kW to W conversion
Manual Configuration
If the Modbus device is not directly supported or if values deviating from the predefined models are to be read or written, the Modbus registers can also be configured manually.
For this purpose, in addition to the general 'modbus' settings (see above), a register
must be defined instead of a value
, as with predefined devices. It is not allowed to specify both value
and register
.
The definition of a register requires the following parameters:
address
: the register addresstype
: The register type, allowed arecoil
,input
,holding
decode
: The type of encoding of the data. Allowed are:int16|32|64, uint16|32|64, float32|64 and u|int32s + float32s
. For typecoil
the encoding is ignored, but must still be specified.bitmask
: An optional specification. The specified value is ANDed with the read value to extract individual bits.
Other allowed parameters of a manual configuration are:
scale
: Floating point number that can be used to convert read values (e.g. W to kW or vice versa). This value is multiplied with the read and decoded raw value.timeout
: modbus timeout. Without unit the value is in ns, otherwise specify unit, e.g. 10s for 10 seconds.
For example:
source: modbus
---
register:
address: 40070
type: holding # coil, holding or input
decode: int32 # int16|32|64, uint16|32|64, float32|64 and u|int32s + float32s
bitmask: 2 # Optional: a bitmask that is applied to the read value. Here the mask is 0000000000000010b, ignored if value is 0
scale: -1.0 # floating point factor applied to result, e.g. for kW to W conversion
timeout: 2s # timeout, without unit in ns
For the int32s/uint32s
decodings, the byte order is swapped, which is useful for E3/DC devices.
Writing Registers
Both holding registers and coils can be written. For this, either type: writeholding
for holding registers or type: writecoil
for coils must be specified.
type: writeholding
always writes a 16-bit register (int or bool16). Therefore, for decode
, uint16
must always be specified.
type: writecoil
writes a coil. Specifications for decode
are ignored.
For example:
source: modbus
---
register:
address: 40070
type: writeholding # writeholding or writecoil
Complete Example
A complete example for a custom charger with modbus interface (here a Phoenix EM-CP-PP-ETH with the IP address 192.168.1.10) could look like this:
For example:
chargers:
- type: custom
name: CustomCharger
status:
# Read the status of the charger
# Either A,B,C or F
source: modbus
id: 180
uri: 192.168.1.10:502
timeout: 3s
register:
address: 100
type: input # Read an input register
decode: int16
enabled:
# Is the charger enabled (1) or not (0)
source: modbus
id: 180
uri: 192.168.1.10:502
register:
address: 400
type: coil # Read a coil
decode: bool16 # Doesn't matter but required
enable:
# Enable the charger
source: modbus
id: 180
uri: 192.168.1.10:502
register:
address: 400
type: writecoil # Write a coil
decode: uint8 # Doesn't matter but required
maxcurrent:
# Set the maximum current
source: modbus
id: 180
uri: 192.168.1.10:502
register:
address: 300
type: writeholding # Write a holding register
decode: uint16