Skip to content
smart charging

Moxa ioLogik E1214

This page shows the nightly version. There is no release version yet.

Connect the relay contacts of the control box to the digital inputs of the module. The module must provide the inputs as discrete inputs (function code 02), a closed contact reads as active.

Parameters

NameDescriptionValueLevel
idModbus ID
Default: 1
intrequired
hostIP address or hostname
Example: 192.0.2.2
required
portPort
Default: 502
intrequired
maxconsumptionpower [W]Guaranteed minimum power (Pmin)

Power limit applied to the root circuit while the limit is active.

optional
w4inputW4 input

Digital input number for the W4 signal (Dimmer for controllable loads), counting from 1 (first input = 1)

Default: 1
optional
w3inputW3 input

Digital input number for the W3 signal (Zero export, 0%), counting from 1 (first input = 1)

Default: 2
optional
productionnominalmax [Wp]Installed generator power

Rated generator/module power of the installation (reference value according to § 9 EEG).

optional
s1inputS1 input

Digital input number for the S1 signal (60% export power limit), counting from 1 (first input = 1)

Example: 3
optional
s2inputS2 input

Digital input number for the S2 signal (30% export power limit), counting from 1 (first input = 1)

Example: 4
optional
Configuration example for evcc.yaml

If you don't want to configure via the UI, you can alternatively use this YAML block.

hems:
type: template
template: fnn-modbus
# Modbus TCP
modbus: tcpip
id: 1
host: # Hostname
port: 502 # Port
maxconsumptionpower: # Guaranteed minimum power (Pmin) (W), Power limit applied to the root circuit while the limit is active.
w4input: 1 # W4 input, Digital input number for the W4 signal (Dimmer for controllable loads), counting from 1 (first input = 1)
w3input: 2 # W3 input, Digital input number for the W3 signal (Zero export, 0%), counting from 1 (first input = 1)
productionnominalmax: # Installed generator power (Wp), Rated generator/module power of the installation (reference value according to § 9 EEG). (optional)
s1input: 3 # S1 input, Digital input number for the S1 signal (60% export power limit), counting from 1 (first input = 1) (optional)
s2input: 4 # S2 input, Digital input number for the S2 signal (30% export power limit), counting from 1 (first input = 1) (optional)