FNN-Steuerbox via EEBus LPC&LPP (§ 14a EnWG, § 9 EEG)

Deze pagina toont de nightly-versie. Schakel over naar de releaseversie.

Parameters

NaamOmschrijvingWaardeNiveau
skiSubject Key Identifier (SKI)

SKI of the FNN control box (shown in its web interface)

optioneel
ipIP address
Voorbeeld: 192.0.2.2
optioneel
productionnominalmax [Wp]Installed generator power

Rated generator/module power of the installation (reference value according to § 9 EEG).

optioneel
consumptionnominalmax [W]Max. consumption power (grid connection)

Contractual maximum power of the grid connection point reported to the control box. This is the connection capacity agreed with the grid operator, NOT the minimum consumption power (Pmin) of the control box.

geavanceerd
failsafeconsumptionpower [W]Failsafe consumption limit (Pmin, LPC)

Failsafe minimum consumption power (Pmin) for controllable loads applied when the heartbeat from the control box is lost; it is overwritten by the control box once it transmits its own failsafe values.

geavanceerd
failsafeproductionpower [W]Failsafe production limit (LPP)

Remaining maximum feed-in power applied when the heartbeat from the control box is lost. Initial value; it is overwritten by the control box once it transmits its own failsafe values.

geavanceerd
failsafedurationFailsafe minimum duration

Minimum time the failsafe limit stays active once entered. Initial value (default 2h); the control box overwrites it once it transmits its own value.

geavanceerd
passthroughpinPassthrough GPIO pin (LPC)

Output pin that mirrors the active LPC signal to an external system

geavanceerd
Configuratievoorbeeld voor evcc.yaml

Als u niet via de gebruikersinterface wilt configureren, kunt u ook dit YAML-blok gebruiken.

hems:
type: template
template: fnn-eebus
ski: # Subject Key Identifier (SKI), SKI of the FNN control box (shown in its web interface)
ip: 192.0.2.2 # IP address, optional
productionnominalmax: # Installed generator power (Wp), Rated generator/module power of the installation (reference value according to § 9 EEG). (optional)
consumptionnominalmax: # Max. consumption power (grid connection) (W), Contractual maximum power of the grid connection point reported to the control box. This is the connection capacity agreed with the grid operator, NOT the minimum consumption power (Pmin) of the control box. (optional)
failsafeconsumptionpower: # Failsafe consumption limit (Pmin, LPC) (W), Failsafe minimum consumption power (Pmin) for controllable loads applied when the heartbeat from the control box is lost; it is overwritten by the control box once it transmits its own failsafe values. (optional)
failsafeproductionpower: # Failsafe production limit (LPP) (W), Remaining maximum feed-in power applied when the heartbeat from the control box is lost. Initial value; it is overwritten by the control box once it transmits its own failsafe values. (optional)
failsafeduration: # Failsafe minimum duration, Minimum time the failsafe limit stays active once entered. Initial value (default 2h); the control box overwrites it once it transmits its own value. (optional)
passthroughpin: # Passthrough GPIO pin (LPC), Output pin that mirrors the active LPC signal to an external system (optional)