Schneider Electric ComPacT NSX (MicroLogic E)

Deze pagina toont de nightly-versie. Schakel over naar de releaseversie.

The trip unit has to be reachable over Modbus through a communication module: IFM (Modbus RTU) or IFE (Modbus TCP), or EIFE on MasterPacT MTZ. IFE and EIFE always use Modbus ID 255, the IFM uses the address set on its rotary switches.

4-pole versions measure the neutral directly. 3-pole versions need an external neutral voltage tap (ENVT) for this, connected and declared in the trip unit (system type 40 or 41). Without ENVT, power values are wrong whenever current flows in the neutral.

The power flow sign has to be set with "EcoStruxure Power Commission" so that the normal direction of flow counts as positive. Factory setting: from the top terminals to the bottom ones.

Gebruik

  • Netmeter
  • Zonne-energieproductie
  • Ladermeter

Parameters

Modbus
NaamOmschrijvingWaardeNiveau
idModbus-ID
Standaard: 1
intverplicht
deviceApparaatnaam

USB-RS485-adapter

Voorbeeld: /dev/ttyUSB0
verplicht
baudrateBaudrate
Standaard: 9600
verplicht
comsetComSet

Communicatieparameter voor de adapter

Standaard: 8N1
verplicht
hostIP-adres of hostnaam
Voorbeeld: 192.0.2.2
verplicht
portPoort
Standaard: 502
intverplicht
Configuratievoorbeeld voor evcc.yaml

Als u niet via de gebruikersinterface wilt configureren, kunt u ook dit YAML-blok gebruiken.

meters:
- name: my_grid
type: template
template: schneider-micrologic
usage: grid
# RS485 via adapter (Modbus RTU)
modbus: rs485serial
id: 255
device: /dev/ttyUSB0 # USB-RS485 Adapter Adresse
baudrate: 19200 # Prüfe die Geräteeinstellungen, typische Werte sind 9600, 19200, 38400, 57600, 115200
comset: "8E1" # Kommunikationsparameter für den Adapter
# RS485 via TCP/IP (Modbus RTU)
modbus: rs485tcpip
id: 255
host: # Hostname
port: 502 # Port
# Modbus TCP
modbus: tcpip
id: 255
host: # Hostname
port: 502 # Port
meters:
- name: my_pv
type: template
template: schneider-micrologic
usage: pv
# RS485 via adapter (Modbus RTU)
modbus: rs485serial
id: 255
device: /dev/ttyUSB0 # USB-RS485 Adapter Adresse
baudrate: 19200 # Prüfe die Geräteeinstellungen, typische Werte sind 9600, 19200, 38400, 57600, 115200
comset: "8E1" # Kommunikationsparameter für den Adapter
# RS485 via TCP/IP (Modbus RTU)
modbus: rs485tcpip
id: 255
host: # Hostname
port: 502 # Port
# Modbus TCP
modbus: tcpip
id: 255
host: # Hostname
port: 502 # Port
meters:
- name: my_charger
type: template
template: schneider-micrologic
usage: charge
# RS485 via adapter (Modbus RTU)
modbus: rs485serial
id: 255
device: /dev/ttyUSB0 # USB-RS485 Adapter Adresse
baudrate: 19200 # Prüfe die Geräteeinstellungen, typische Werte sind 9600, 19200, 38400, 57600, 115200
comset: "8E1" # Kommunikationsparameter für den Adapter
# RS485 via TCP/IP (Modbus RTU)
modbus: rs485tcpip
id: 255
host: # Hostname
port: 502 # Port
# Modbus TCP
modbus: tcpip
id: 255
host: # Hostname
port: 502 # Port