FNN-Steuerbox via GPIO (§ 14a EnWG, § 9 EEG)
Parametri
| Nome | Descrizione | Valore | Livello |
|---|---|---|---|
maxconsumptionpower [W] | Guaranteed minimum power (Pmin) Power limit applied to the root circuit while the limit is active. | facoltativo | |
w4pin | W4 GPIO pin Input pin for the W4 signal (Dimmer for controllable loads) | facoltativo | |
w3pin | W3 GPIO pin Input pin for the W3 signal (Zero export, 0%) | facoltativo | |
productionnominalmax [Wp] | Installed generator power Rated generator/module power of the installation (reference value according to § 9 EEG). | facoltativo | |
s1pin | S1 GPIO pin Input pin for the S1 signal (60% export power limit) | facoltativo | |
s2pin | S2 GPIO pin Input pin for the S2 signal (30% export power limit) | facoltativo | |
activelow | Inputs active low Signals are active when the input is pulled to ground, e.g. by a relay contact switching to GND. | avanzato | |
bias | Input bias Internal pull resistor of the inputs. Determines the input level while the contact is open. | avanzato |
Esempio di configurazione per evcc.yaml
Se preferisci non configurare il dispositivo dall’interfaccia, puoi usare questo blocco YAML.
hems: type: template template: fnn-gpio maxconsumptionpower: # Guaranteed minimum power (Pmin) (W), Power limit applied to the root circuit while the limit is active. w4pin: # W4 GPIO pin, Input pin for the W4 signal (Dimmer for controllable loads) w3pin: # W3 GPIO pin, Input pin for the W3 signal (Zero export, 0%) productionnominalmax: # Installed generator power (Wp), Rated generator/module power of the installation (reference value according to § 9 EEG). (optional) s1pin: # S1 GPIO pin, Input pin for the S1 signal (60% export power limit) (optional) s2pin: # S2 GPIO pin, Input pin for the S2 signal (30% export power limit) (optional) activelow: # Inputs active low, Signals are active when the input is pulled to ground, e.g. by a relay contact switching to GND. (optional) bias: pull-up # Input bias, Internal pull resistor of the inputs. Determines the input level while the contact is open. [pull-up, pull-down, disabled, as-is] (optional)