Moxa ioLogik E1242
Connect the relay contacts of the control box to the digital inputs of the module. The module must provide the inputs as discrete inputs (function code 02), a closed contact reads as active.
Parametri
| Nome | Descrizione | Valore | Livello |
|---|---|---|---|
id | ID Modbus | int | obbligatorio |
host | Indirizzo IP o hostname | obbligatorio | |
port | Porta | int | obbligatorio |
maxconsumptionpower [W] | Guaranteed minimum power (Pmin) Power limit applied to the root circuit while the limit is active. | facoltativo | |
w4input | W4 input Digital input number for the W4 signal (Dimmer for controllable loads), counting from 1 (first input = 1) | facoltativo | |
w3input | W3 input Digital input number for the W3 signal (Zero export, 0%), counting from 1 (first input = 1) | facoltativo | |
productionnominalmax [Wp] | Installed generator power Rated generator/module power of the installation (reference value according to § 9 EEG). | facoltativo | |
s1input | S1 input Digital input number for the S1 signal (60% export power limit), counting from 1 (first input = 1) | facoltativo | |
s2input | S2 input Digital input number for the S2 signal (30% export power limit), counting from 1 (first input = 1) | facoltativo |
Esempio di configurazione per evcc.yaml
Se preferisci non configurare il dispositivo dall’interfaccia, puoi usare questo blocco YAML.
hems: type: template template: fnn-modbus
# Modbus TCP modbus: tcpip id: 1 host: # Hostname port: 502 # Port maxconsumptionpower: # Guaranteed minimum power (Pmin) (W), Power limit applied to the root circuit while the limit is active. w4input: 1 # W4 input, Digital input number for the W4 signal (Dimmer for controllable loads), counting from 1 (first input = 1) w3input: 2 # W3 input, Digital input number for the W3 signal (Zero export, 0%), counting from 1 (first input = 1) productionnominalmax: # Installed generator power (Wp), Rated generator/module power of the installation (reference value according to § 9 EEG). (optional) s1input: 3 # S1 input, Digital input number for the S1 signal (60% export power limit), counting from 1 (first input = 1) (optional) s2input: 4 # S2 input, Digital input number for the S2 signal (30% export power limit), counting from 1 (first input = 1) (optional)