LG Therma V R290 Monobloc (SG Ready)

Questa pagina mostra la versione nightly. Passa alla versione release.

Modbus connection to LG Therma V heat pump. Uses SG Ready energy states for intelligent control. Set the indoor unit in the installer settings > "Connectivity" > "Energy state" > "ESS use type" > to "Modbus". Since the internal power measurement shows too high values, an external power measurement is suggested. Factory setting Modbus (HEX) = 21 (33). Modbus registers can be found within the installation manual (address without the leading number and -1). Information on the energy state can be found within the installation manual. Energy states 6 and 7 can be adapted at the indoor unit in the installer settings > "Connectivity" > "Energy state" >"Energy state definition". If the internal power measurement does not work (not all models support this register), please set energy metering to "false".

Funzionalità supportate

  • Riducibile: La potenza assorbita può essere ridotta (ad es. § 14a EnWG). Vedi Limite esterno.

Parametri

Modbus
NomeDescrizioneValoreLivello
idID Modbus
Predefinito: 1
intobbligatorio
deviceNome dispositivo

Adattatore USB-RS485

Esempio: /dev/ttyUSB0
obbligatorio
baudrateBaudrate
Predefinito: 9600
obbligatorio
comsetComSet

Parametro di comunicazione dell’adattatore

Predefinito: 8N1
obbligatorio
hostIndirizzo IP o hostname
Esempio: 192.0.2.2
obbligatorio
portPorta
Predefinito: 502
intobbligatorio
tempsourceDHW warm water tank or inlet flow temperature
Predefinito: water_tank
facoltativo
energystateSGReady states or modifyable energy state 6 and 7
Predefinito: SGReady
facoltativo
haspowerInternal energy metering
Predefinito: true
facoltativo
Esempio di configurazione per evcc.yaml

Se preferisci non configurare il dispositivo dall’interfaccia, puoi usare questo blocco YAML.

chargers:
- name: my_heating
type: template
template: lg-therma
# RS485 via adapter (Modbus RTU)
modbus: rs485serial
id: 33
device: /dev/ttyUSB0 # USB-RS485 Adapter Adresse
baudrate: 9600 # Prüfe die Geräteeinstellungen, typische Werte sind 9600, 19200, 38400, 57600, 115200
comset: "8N1" # Kommunikationsparameter für den Adapter
# RS485 via TCP/IP (Modbus RTU)
modbus: rs485tcpip
id: 33
host: # Hostname
port: 502 # Port
tempsource: water_tank # DHW warm water tank or inlet flow temperature, [water_tank, water_inlet]
energystate: SGReady # SGReady states or modifyable energy state 6 and 7, [SGReady, IndividualEnergystate]
haspower: true # Internal energy metering