The trip unit has to be reachable over Modbus through a communication module: IFM (Modbus RTU) or IFE (Modbus TCP), or EIFE on MasterPacT MTZ. IFE and EIFE always use Modbus ID 255, the IFM uses the address set on its rotary switches.

4-pole versions measure the neutral directly. 3-pole versions need an external neutral voltage tap (ENVT) for this, connected and declared in the trip unit (system type 40 or 41). Without ENVT, power values are wrong whenever current flows in the neutral.

The power flow sign has to be set with "EcoStruxure Power Commission" so that the normal direction of flow counts as positive. Factory setting: from the top terminals to the bottom ones.

Ambiti di utilizzo

  • Contatore di rete
  • Produzione solare
  • Contatore del caricabatterie

Parametri

Modbus
NomeDescrizioneValoreLivello
idID Modbus
Predefinito: 1
intobbligatorio
deviceNome dispositivo

Adattatore USB-RS485

Esempio: /dev/ttyUSB0
obbligatorio
baudrateBaudrate
Predefinito: 9600
obbligatorio
comsetComSet

Parametro di comunicazione dell’adattatore

Predefinito: 8N1
obbligatorio
hostIndirizzo IP o hostname
Esempio: 192.0.2.2
obbligatorio
portPorta
Predefinito: 502
intobbligatorio
Esempio di configurazione per evcc.yaml

Se preferisci non configurare il dispositivo dall’interfaccia, puoi usare questo blocco YAML.

meters:
- name: my_grid
type: template
template: schneider-micrologic
usage: grid
# RS485 via adapter (Modbus RTU)
modbus: rs485serial
id: 255
device: /dev/ttyUSB0 # USB-RS485 Adapter Adresse
baudrate: 19200 # Prüfe die Geräteeinstellungen, typische Werte sind 9600, 19200, 38400, 57600, 115200
comset: "8E1" # Kommunikationsparameter für den Adapter
# RS485 via TCP/IP (Modbus RTU)
modbus: rs485tcpip
id: 255
host: # Hostname
port: 502 # Port
# Modbus TCP
modbus: tcpip
id: 255
host: # Hostname
port: 502 # Port
meters:
- name: my_pv
type: template
template: schneider-micrologic
usage: pv
# RS485 via adapter (Modbus RTU)
modbus: rs485serial
id: 255
device: /dev/ttyUSB0 # USB-RS485 Adapter Adresse
baudrate: 19200 # Prüfe die Geräteeinstellungen, typische Werte sind 9600, 19200, 38400, 57600, 115200
comset: "8E1" # Kommunikationsparameter für den Adapter
# RS485 via TCP/IP (Modbus RTU)
modbus: rs485tcpip
id: 255
host: # Hostname
port: 502 # Port
# Modbus TCP
modbus: tcpip
id: 255
host: # Hostname
port: 502 # Port
meters:
- name: my_charger
type: template
template: schneider-micrologic
usage: charge
# RS485 via adapter (Modbus RTU)
modbus: rs485serial
id: 255
device: /dev/ttyUSB0 # USB-RS485 Adapter Adresse
baudrate: 19200 # Prüfe die Geräteeinstellungen, typische Werte sind 9600, 19200, 38400, 57600, 115200
comset: "8E1" # Kommunikationsparameter für den Adapter
# RS485 via TCP/IP (Modbus RTU)
modbus: rs485tcpip
id: 255
host: # Hostname
port: 502 # Port
# Modbus TCP
modbus: tcpip
id: 255
host: # Hostname
port: 502 # Port