Schneider Electric MasterPacT MTZ (MicroLogic X)

The trip unit has to be reachable over Modbus through a communication module: IFM (Modbus RTU) or IFE (Modbus TCP), or EIFE on MasterPacT MTZ. IFE and EIFE always use Modbus ID 255, the IFM uses the address set on its rotary switches.

4-pole versions measure the neutral directly. 3-pole versions need an external neutral voltage tap (ENVT) for this, connected and declared in the trip unit (system type 40 or 41). Without ENVT, power values are wrong whenever current flows in the neutral.

The power flow sign has to be set with "EcoStruxure Power Commission" so that the normal direction of flow counts as positive. Factory setting: from the top terminals to the bottom ones.

Domaines d’utilisation

  • Compteur avant réseau
  • Production solaire
  • Compteur du chargeur

Paramètres

Modbus
NomDescriptionValeurNiveau
idID Modbus
Par défaut: 1
intobligatoire
deviceNom du périphérique

Adaptateur USB-RS485

Exemple: /dev/ttyUSB0
obligatoire
baudrateDébit en bauds
Par défaut: 9600
obligatoire
comsetComSet

Paramètre de communication de l’adaptateur

Par défaut: 8N1
obligatoire
hostAdresse IP ou nom d’hôte
Exemple: 192.0.2.2
obligatoire
portPort
Par défaut: 502
intobligatoire
Exemple de configuration pour evcc.yaml

Si vous ne souhaitez pas passer par l’interface, vous pouvez utiliser ce bloc YAML à la place.

meters:
- name: my_grid
type: template
template: schneider-micrologic
usage: grid
# RS485 via adapter (Modbus RTU)
modbus: rs485serial
id: 255
device: /dev/ttyUSB0 # USB-RS485 Adapter Adresse
baudrate: 19200 # Prüfe die Geräteeinstellungen, typische Werte sind 9600, 19200, 38400, 57600, 115200
comset: "8E1" # Kommunikationsparameter für den Adapter
# RS485 via TCP/IP (Modbus RTU)
modbus: rs485tcpip
id: 255
host: # Hostname
port: 502 # Port
# Modbus TCP
modbus: tcpip
id: 255
host: # Hostname
port: 502 # Port
meters:
- name: my_pv
type: template
template: schneider-micrologic
usage: pv
# RS485 via adapter (Modbus RTU)
modbus: rs485serial
id: 255
device: /dev/ttyUSB0 # USB-RS485 Adapter Adresse
baudrate: 19200 # Prüfe die Geräteeinstellungen, typische Werte sind 9600, 19200, 38400, 57600, 115200
comset: "8E1" # Kommunikationsparameter für den Adapter
# RS485 via TCP/IP (Modbus RTU)
modbus: rs485tcpip
id: 255
host: # Hostname
port: 502 # Port
# Modbus TCP
modbus: tcpip
id: 255
host: # Hostname
port: 502 # Port
meters:
- name: my_charger
type: template
template: schneider-micrologic
usage: charge
# RS485 via adapter (Modbus RTU)
modbus: rs485serial
id: 255
device: /dev/ttyUSB0 # USB-RS485 Adapter Adresse
baudrate: 19200 # Prüfe die Geräteeinstellungen, typische Werte sind 9600, 19200, 38400, 57600, 115200
comset: "8E1" # Kommunikationsparameter für den Adapter
# RS485 via TCP/IP (Modbus RTU)
modbus: rs485tcpip
id: 255
host: # Hostname
port: 502 # Port
# Modbus TCP
modbus: tcpip
id: 255
host: # Hostname
port: 502 # Port