KACO blueplanet hybrid NH3
For KACO blueplanet Hybrid NH3 with AI dongle/Wi-Fi stick. Modbus TCP and the local AISWEI HTTP API must be reachable at the stick's IP address (Modbus TCP port 502, device ID 3; HTTP port 8484).
Battery power control uses the local fdbg.cgi endpoint. Maximum charge and discharge power are read from SunSpec Model 802. Battery charge and discharge energy are read from the local AISWEI HTTP API.
Configure curtailment through a separate KACO NH3 curtailer device.
The grid meter exposed through SunSpec Model 203 provides grid power, import/export energy, and per-phase measurements.
Fonctionnalités prises en charge
- Pilotage de la batterie: Pilotage externe de la charge et de la décharge de la batterie domestique par evcc.
Domaines d’utilisation
- Compteur avant réseau
- Production solaire
- Batterie
Paramètres
| Nom | Description | Valeur | Niveau |
|---|---|---|---|
id | ID Modbus | int | obligatoire |
host | Adresse IP ou nom d’hôte | obligatoire | |
port | Port | int | obligatoire |
battery | Battery number | facultatif | |
serial | Inverter serial number (isn) | facultatif | |
capacity [kWh] | Battery capacity | facultatif | |
minsoc [%] | Minimum charge Written to the inverter as the discharge limit and used by the optimizer. Only set a value supported by the battery. Minimum value is 5%. | facultatif | |
maxsoc [%] | Maximum charge Written to the inverter as the charge limit and used by the optimizer. Only set a value supported by the battery. | facultatif |
Exemple de configuration pour evcc.yaml
Si vous ne souhaitez pas passer par l’interface, vous pouvez utiliser ce bloc YAML à la place.
meters: - name: my_grid type: template template: kaco-nh3 usage: grid
# Modbus TCP modbus: tcpip id: 3 host: # Hostname port: 502 # Portmeters: - name: my_pv type: template template: kaco-nh3 usage: pv
# Modbus TCP modbus: tcpip id: 3 host: # Hostname port: 502 # Portmeters: - name: my_battery type: template template: kaco-nh3 usage: battery
# Modbus TCP modbus: tcpip id: 3 host: # Hostname port: 502 # Port battery: # Battery number, [1, 2] serial: # Inverter serial number (isn) capacity: 50 # Battery capacity (kWh), optional minsoc: 10 # Minimum charge (%), Written to the inverter as the discharge limit and used by the optimizer. Only set a value supported by the battery. Minimum value is 5%. (optional) maxsoc: 100 # Maximum charge (%), Written to the inverter as the charge limit and used by the optimizer. Only set a value supported by the battery. (optional)